Bradley S19-324DGW Emergency Signaling System, Drench or Combination, Green Beacon, Class I. Each

filler

Price:
Sale priceCAD $6,100.00

Description

  • White area light included in S19-324DGW
  • Automatic, audible and visual system
  • Double pole, double throw flow switch
  • Designed to meet NEMA No. 4XCode
  • Easily connected to other Emergency Fixture units
  • Halogen steady state beacon light
  • Silence switch with auto reset
  • For indoor and outdoor applications
  • Universal AC voltage...

Specifications:

System can be easily connected to most combination drench shower/eyewash
or drench shower units which have 1" NPT inlet piping and a 30 GPM
water inlet source. If fixture is top-supplied, adequate space must be provided
for vertical orientation of sensor. Consult installation manual for specific
requirements. Remote location hookup possible by using the contacts in the
flow switch junction box or central control box.


Standard Equipment:

Central Control
Emergency fixture signaling system operates from one central control board.
The central control offers several different easy to connect inputs and outputs,
allowing for direct connection to a building management system and runs
on a safe, 24v system. Electrical components are contained with a NEMA 4X
enclosure.
Remote Wiring
Remote location hookup possible by using contacts in the central control
board or contacts in the flow switch junction box.
Horn Sound
Piezo fast beep sound. 108 dB at 2 feet to cut through ambient noise.
Signal Light
Safety amber-colored glass. Dust cover. All solid state components with no
moving parts for maintenance-free operation.


Voltage:

Universal AC Input: 90-264 AC, 50-60 Hz. Max 70 Watts. Max 3.0 Amps.
Flow Switch Activation
Watertight and completely assembled for easy hookup to signaling assembly.
Double pole, double throw flow switch in brass construction.
Electrical Connection
Prewired, 6-foot multiple conductor, quick-connect, waterproof cable for easy
connection to the signaling system.
Pipe Size
1" NPT supply.
Mounting
Signaling system can be mounted to fixture piping, an adjacent wall or heat
trace unit.